ControlForge SNMP Protocol Guide

James M. Belcher Founder, JMB Technical Services LLC April 2026 | ControlForge v1.0.533


1. Architecture Overview

ControlForge implements a complete SNMP stack — client, trap receiver, and agent (server) — callable directly from IEC 61131-3 Structured Text. No MIB compilers, no external tools, no configuration files. You poll network devices, catch traps, and expose PLC data via SNMP with plain function calls in your ST programs.

RoleFunctionsUse Case
ClientSNMP_CLIENT_CREATE / SNMP_GET / SNMP_SET / SNMP_WALKPoll UPS, PDU, switches, printers — any SNMP-managed device
Trap ReceiverSNMP_TRAP_START / SNMP_TRAP_GET_BUFFERCatch asynchronous alerts: link down, UPS on battery, temperature alarms
Agent (Server)SNMP_AGENT_CREATE / SNMP_AGENT_SET_INT / SNMP_AGENT_SET_STRExpose PLC tags to NMS platforms: Nagios, PRTG, Zabbix, LibreNMS

All three roles run simultaneously. A single ControlForge instance can poll a datacenter UPS and PDU as a client, receive traps from managed switches, and serve its own OID tree to a network management system — all from the same ST program.

System Diagram

SNMP Versions Supported

VersionAuthPrivacyControlForge Support
v1Community stringNoneClient only
v2cCommunity stringNoneClient, Agent, Traps
v3USM (MD5/SHA)DES/AESClient only (SNMPv3 auth+priv)

Built-in OID Constants

ControlForge provides named constants for common OIDs so you never need to memorize dotted notation:

ConstantOIDDescription
SNMP_OID_SYS_DESCR1.3.6.1.2.1.1.1.0System description
SNMP_OID_SYS_OBJECT_ID1.3.6.1.2.1.1.2.0System object identifier
SNMP_OID_SYS_UPTIME1.3.6.1.2.1.1.3.0Uptime in hundredths of seconds
SNMP_OID_SYS_CONTACT1.3.6.1.2.1.1.4.0Admin contact
SNMP_OID_SYS_NAME1.3.6.1.2.1.1.5.0Device hostname
SNMP_OID_SYS_LOCATION1.3.6.1.2.1.1.6.0Physical location
SNMP_OID_IF_NUMBER1.3.6.1.2.1.2.1.0Number of network interfaces
SNMP_OID_IF_TABLE1.3.6.1.2.1.2.2Interface table root
SNMP_OID_UPS_BATTERY_STATUS1.3.6.1.2.1.33.1.2.1.0UPS battery status
SNMP_OID_UPS_INPUT_VOLTAGE1.3.6.1.2.1.33.1.3.3.1.3.1UPS input voltage
SNMP_OID_UPS_OUTPUT_LOAD1.3.6.1.2.1.33.1.4.4.1.5.1UPS output load percentage

2. Client Functions

2.1 Connection Lifecycle

SNMP_CLIENT_CREATE -- Create v1/v2c Client

(* Minimal — defaults to port 161, community "public", version v2c *)
ok := SNMP_CLIENT_CREATE('ups1', '10.0.1.50');

(* Explicit port and community *)
ok := SNMP_CLIENT_CREATE('pdu1', '10.0.1.51', 161, 'datacenter-ro', 'v2c');

(* SNMPv1 device *)
ok := SNMP_CLIENT_CREATE('old_switch', '10.0.1.10', 161, 'public', 'v1');
ParamTypeDefaultDescription
nameSTRING(required)Unique client identifier
hostSTRING(required)IP address or hostname
portINT161UDP port
communitySTRING'public'Community string
versionSTRING'v2c''v1' or 'v2c'

Returns: BOOL -- TRUE on success.

SNMP_CLIENT_CREATE_V3 -- Create v3 Client (AuthPriv)

ok := SNMP_CLIENT_CREATE_V3('secure_switch', '10.0.1.20',
'snmpAdmin', (* USM username *)
'SHA', (* auth protocol: MD5 or SHA *)
'authPass123!', (* auth passphrase *)
'AES', (* privacy protocol: DES or AES *)
'privPass456!'); (* privacy passphrase *)
ParamTypeDescription
nameSTRINGUnique client identifier
hostSTRINGIP address or hostname
userSTRINGUSM username
authProtoSTRING'MD5' or 'SHA'
authPassSTRINGAuthentication passphrase (min 8 chars)
privProtoSTRING'DES' or 'AES'
privPassSTRINGPrivacy passphrase (min 8 chars)

Returns: BOOL -- TRUE on success.

Security Note: SNMPv3 with AuthPriv encrypts the entire PDU. Use this for any SNMP communication crossing untrusted networks. Community strings in v1/v2c travel in plaintext.

SNMP_CLIENT_CONNECT -- Establish Connection

ok := SNMP_CLIENT_CONNECT('ups1');

Opens the UDP socket and starts the background poll loop. The client automatically polls all OIDs retrieved via SNMP_GET on a configurable interval, caching results for fast access from cyclic ST programs.

Returns: BOOL -- TRUE on success.

SNMP_CLIENT_DISCONNECT -- Close Connection

ok := SNMP_CLIENT_DISCONNECT('ups1');

Stops polling and closes the UDP socket. The client can be reconnected later with SNMP_CLIENT_CONNECT.

Returns: BOOL -- TRUE on success.

SNMP_CLIENT_IS_CONNECTED -- Check Status

IF SNMP_CLIENT_IS_CONNECTED('ups1') THEN
(* Safe to read cached values *)
END_IF;

Returns: BOOL -- TRUE if connected and polling.


2.2 Reading Values

SNMP_GET -- Read Single OID (from Poll Cache)

(* Using built-in OID constant *)
descr := SNMP_GET('ups1', SNMP_OID_SYS_DESCR);
(* Returns: 'APC Smart-UPS 3000 RM' *)

(* Using dotted OID string *)
voltage := SNMP_GET('ups1', '1.3.6.1.2.1.33.1.3.3.1.3.1');
(* Returns: 120 (integer) *)

(* Using built-in UPS constant *)
load := SNMP_GET('ups1', SNMP_OID_UPS_OUTPUT_LOAD);
(* Returns: 47 (percent) *)
ParamTypeDescription
nameSTRINGClient name
oidStrSTRINGOID in dotted notation or built-in constant

Returns: ANY -- The value from the poll cache. Type depends on the MIB object: STRING for DisplayString, INT for Integer32/Gauge32/Counter32, etc.

Important: SNMP_GET reads from the local poll cache, not the network. This makes it safe to call from fast cyclic tasks (1-10ms) without blocking. The background poller updates the cache asynchronously.

SNMP_GET_MULTIPLE -- Read Multiple OIDs at Once

result := SNMP_GET_MULTIPLE('ups1',
SNMP_OID_SYS_NAME + ',' + SNMP_OID_SYS_UPTIME + ',' + SNMP_OID_UPS_BATTERY_STATUS);
(* Returns: MAP with OID keys and their values *)
(* {"1.3.6.1.2.1.1.5.0": "UPS-DC-RACK1",
"1.3.6.1.2.1.1.3.0": 8640000,
"1.3.6.1.2.1.33.1.2.1.0": 2} *)
ParamTypeDescription
nameSTRINGClient name
oidStrsSTRINGComma-separated OID strings

Returns: MAP -- OID-to-value mapping from cache.

SNMP_GET_NEXT -- Get Next OID in Tree

result := SNMP_GET_NEXT('ups1', '1.3.6.1.2.1.1.1');
(* Returns: MAP with "oid" and "value" keys *)
(* {"oid": "1.3.6.1.2.1.1.1.0", "value": "APC Smart-UPS 3000"} *)
ParamTypeDescription
nameSTRINGClient name
oidStrSTRINGStarting OID

Returns: MAP -- Contains oid (the next OID) and value.

SNMP_WALK -- Walk an OID Subtree (BulkWalk)

(* Walk the entire interface table *)
interfaces := SNMP_WALK('switch1', SNMP_OID_IF_TABLE);
(* Returns: []MAP — array of {oid, value} pairs *)
(* [{"oid": "1.3.6.1.2.1.2.2.1.1.1", "value": 1},
{"oid": "1.3.6.1.2.1.2.2.1.2.1", "value": "GigabitEthernet0/1"},
{"oid": "1.3.6.1.2.1.2.2.1.5.1", "value": 1000000000},
...] *)
ParamTypeDescription
nameSTRINGClient name
rootOidStrSTRINGRoot OID to walk from

Returns: []MAP -- Array of {oid, value} pairs. Uses SNMP GETBULK (v2c/v3) for efficiency.

Performance: Walk operations are not cached — they execute a live SNMP BulkWalk on the network. Use them for discovery or infrequent polling, not in fast cyclic tasks.


2.3 Convenience Getters

These wrap SNMP_GET with the appropriate system OID for cleaner code:

descr := SNMP_GET_SYS_DESCR('ups1'); (* System description *)
name := SNMP_GET_SYS_NAME('ups1'); (* Device hostname *)
uptime := SNMP_GET_SYS_UPTIME('ups1'); (* Uptime in hundredths of seconds *)
location := SNMP_GET_SYS_LOCATION('ups1'); (* Physical location string *)
contact := SNMP_GET_SYS_CONTACT('ups1'); (* Admin contact string *)

Each returns the same type as the underlying SNMP_GET call.


2.4 Writing Values

SNMP_SET -- Write a Value to a Remote Device

(* Set the system contact string *)
ok := SNMP_SET('switch1', SNMP_OID_SYS_CONTACT, 'OctetString', 'ops@example.com');

(* Set an integer value *)
ok := SNMP_SET('pdu1', '1.3.6.1.4.1.318.1.1.4.4.2.1.3.1', 'Integer', 1);
(* APC PDU: outlet 1 immediate ON *)
ParamTypeDescription
nameSTRINGClient name
oidStrSTRINGTarget OID
valueTypeSTRINGSNMP type: 'Integer', 'OctetString', 'ObjectIdentifier', 'IPAddress', 'Counter32', 'Gauge32', 'TimeTicks'
valueANYValue to write

Returns: BOOL -- TRUE on success.

Write Access: Most devices require a read-write community string (often 'private'). SNMPv3 write access depends on USM user VACM configuration on the target device.


2.5 Client Management

SNMP_CLIENT_GET_STATS -- Connection Statistics

stats := SNMP_CLIENT_GET_STATS('ups1');
(* Returns: MAP *)
(* {"requests_sent": 1847, "responses_received": 1845,
"timeouts": 2, "errors": 0, "last_poll_ms": 3} *)

Returns: MAP -- Request counts, error counts, and timing.

SNMP_CLIENT_DELETE -- Remove Client

ok := SNMP_CLIENT_DELETE('ups1');

Disconnects (if connected) and removes the client instance. Frees all associated resources.

Returns: BOOL -- TRUE on success.

SNMP_CLIENT_LIST -- List All Clients

clients := SNMP_CLIENT_LIST();
(* Returns: ['ups1', 'pdu1', 'switch1'] *)

Returns: List of client names.


3. Trap Receiver

The trap receiver listens for asynchronous SNMP notifications (traps and informs) from managed devices. Incoming traps are buffered in a ring buffer that your ST program drains on each scan cycle.

3.1 Trap Lifecycle

SNMP_TRAP_START -- Start Listening

(* Listen on standard trap port with default community *)
ok := SNMP_TRAP_START('datacenter_traps', 162);

(* Restrict to specific communities *)
ok := SNMP_TRAP_START('secure_traps', 1162, 'monitoring-rw,datacenter-ro');
ParamTypeDefaultDescription
nameSTRING(required)Unique receiver identifier
portINT(required)UDP listen port (162 = standard, use 1162+ if unprivileged)
communitiesSTRING(all)Comma-separated allowed community strings; empty = accept all

Returns: BOOL -- TRUE on success.

Port 162: On Linux, binding to ports below 1024 requires root or CAP_NET_BIND_SERVICE. Run ControlForge with appropriate capabilities or use a port above 1024.

SNMP_TRAP_STOP -- Stop Listening

ok := SNMP_TRAP_STOP('datacenter_traps');

Returns: BOOL -- TRUE on success.

SNMP_TRAP_IS_RUNNING -- Check Receiver Status

IF SNMP_TRAP_IS_RUNNING('datacenter_traps') THEN
(* Receiver is active *)
END_IF;

Returns: BOOL -- TRUE if listening.

SNMP_TRAP_GET_STATS -- Receiver Statistics

stats := SNMP_TRAP_GET_STATS('datacenter_traps');
(* Returns: MAP *)
(* {"traps_received": 42, "traps_dropped": 0,
"buffer_size": 1000, "buffer_used": 3} *)

Returns: MAP -- Trap counts and buffer utilization.


3.2 Reading Traps

SNMP_TRAP_GET_BUFFER -- Drain All Buffered Traps

One buffer per runtime. Trap receivers are named — SNMP_TRAP_START, SNMP_TRAP_STOP, SNMP_TRAP_IS_RUNNING and SNMP_TRAP_GET_STATS all take a name — but every receiver feeds a single shared buffer, so the buffer calls take no name. Each trap record carries its source, which is how you tell them apart. Per-receiver buffers are on the deferred list in TODO.md.

traps := SNMP_TRAP_GET_BUFFER();
(* Returns: []MAP — array of trap records *)
(* [{"timestamp": "2026-04-03T14:22:01Z",
"source": "10.0.1.50",
"community": "public",
"enterprise": "1.3.6.1.4.1.318",
"generic_trap": 6,
"specific_trap": 1,
"varbinds": [
{"oid": "1.3.6.1.2.1.33.1.2.1.0", "type": "Integer", "value": 3},
{"oid": "1.3.6.1.2.1.33.1.2.2.0", "type": "Integer", "value": 45}
]},
...] *)

Returns: []MAP -- Array of trap records. Each contains:

FieldTypeDescription
timestampSTRINGISO 8601 receive time
sourceSTRINGSender IP address
communitySTRINGCommunity string from trap PDU
enterpriseSTRINGEnterprise OID (v1 traps)
generic_trapINTGeneric trap type (v1) or SNMPv2 notification OID
specific_trapINTEnterprise-specific trap code (v1)
varbinds[]MAPVariable bindings: {oid, type, value}

Buffer Behavior: SNMP_TRAP_GET_BUFFER returns all buffered traps and clears them atomically. Call it once per scan cycle to avoid processing duplicates.

SNMP_TRAP_GET_COUNT -- Check Buffer Depth

count := SNMP_TRAP_GET_COUNT();
IF count > 0 THEN
traps := SNMP_TRAP_GET_BUFFER();
(* Process traps *)
END_IF;

Returns: INT -- Number of traps currently buffered.

SNMP_TRAP_CLEAR_BUFFER -- Discard All Buffered Traps

SNMP_TRAP_CLEAR_BUFFER();

Discards all buffered traps without processing. Useful after reconnection or during initialization when stale traps are not relevant.


4. Agent (Server) Functions

The SNMP agent exposes ControlForge data as an OID tree that any NMS or monitoring tool can poll. You register OIDs with typed values, and the agent responds to GET/GETNEXT/GETBULK requests automatically.

4.1 Agent Lifecycle

SNMP_AGENT_CREATE -- Create Agent

(* Minimal — defaults to community "public" *)
ok := SNMP_AGENT_CREATE('plc_agent', 1161);

(* Full configuration *)
ok := SNMP_AGENT_CREATE('plc_agent', 1161, 'monitoring-ro',
'ControlForge v1.0.533 SNMP Agent', (* sysDescr *)
'PLC-RACK1'); (* sysName *)
ParamTypeDefaultDescription
nameSTRING(required)Unique agent identifier
portINT(required)UDP listen port
communitySTRING'public'Required community string for access
sysDescrSTRING''Value returned for sysDescr.0 OID
sysNameSTRING''Value returned for sysName.0 OID

Returns: BOOL -- TRUE on success.

SNMP_AGENT_START -- Begin Serving

ok := SNMP_AGENT_START('plc_agent');

Starts the UDP listener. The agent responds to SNMP GET, GETNEXT, and GETBULK requests for any OID you have registered.

Returns: BOOL -- TRUE on success.

SNMP_AGENT_STOP -- Stop Serving

ok := SNMP_AGENT_STOP('plc_agent');

Returns: BOOL -- TRUE on success.

SNMP_AGENT_IS_RUNNING -- Check Status

IF SNMP_AGENT_IS_RUNNING('plc_agent') THEN
(* Agent is serving requests *)
END_IF;

Returns: BOOL -- TRUE if listening.


4.2 Setting OID Values

Register OIDs and update their values from your ST program. The agent serves these values to any NMS that polls them.

SNMP_AGENT_SET_INT -- Set Integer OID

(* Expose production count as a standard integer *)
ok := SNMP_AGENT_SET_INT('plc_agent', '1.3.6.1.4.1.99999.1.1.0', production_count);
ParamTypeDescription
nameSTRINGAgent name
oidStrSTRINGOID to register/update
valueINTInteger value

Returns: BOOL -- TRUE on success.

SNMP_AGENT_SET_GAUGE -- Set Gauge32 OID

(* Expose temperature — Gauge32 never wraps, suitable for measurements *)
ok := SNMP_AGENT_SET_GAUGE('plc_agent', '1.3.6.1.4.1.99999.1.2.0', tank_temp_x10);

Gauge32 values represent a current measurement that can increase or decrease (temperature, pressure, level). Unlike Counter32, they do not wrap.

Returns: BOOL -- TRUE on success.

SNMP_AGENT_SET_COUNTER -- Set Counter32 OID

(* Expose total parts — Counter32 monotonically increases and wraps at 2^32 *)
ok := SNMP_AGENT_SET_COUNTER('plc_agent', '1.3.6.1.4.1.99999.1.3.0', total_parts);

Counter32 values represent monotonically increasing counts (packets, parts, errors). NMS tools calculate rates from counter deltas.

Returns: BOOL -- TRUE on success.

SNMP_AGENT_SET_STR -- Set OctetString OID

(* Expose machine state as a human-readable string *)
ok := SNMP_AGENT_SET_STR('plc_agent', '1.3.6.1.4.1.99999.1.4.0', 'RUNNING');

(* Expose alarm description *)
ok := SNMP_AGENT_SET_STR('plc_agent', '1.3.6.1.4.1.99999.1.5.0', active_alarm_text);

Returns: BOOL -- TRUE on success.


4.3 Reading OID Values

SNMP_AGENT_GET_INT -- Read Back an Integer OID

current := SNMP_AGENT_GET_INT('plc_agent', '1.3.6.1.4.1.99999.1.1.0');

Returns: INT -- Current value of the registered OID. Returns 0 if the OID is not registered.


4.4 Agent Management

SNMP_AGENT_DELETE -- Remove Agent

ok := SNMP_AGENT_DELETE('plc_agent');

Stops (if running) and removes the agent instance.

Returns: BOOL -- TRUE on success.

SNMP_AGENT_LIST -- List All Agents

agents := SNMP_AGENT_LIST();
(* Returns: ['plc_agent'] *)

Returns: List of agent names.


5. Enterprise OID Design

When exposing PLC data via the SNMP agent, you need a private enterprise OID subtree. Register one at IANA PEN or use a test range.

1.3.6.1.4.1.<YOUR_PEN>
.1 — System
.1.0 sysState INTEGER (0=Stopped, 1=Running, 2=Faulted)
.2.0 sysVersion STRING "1.0.520"
.3.0 sysScanTimeUs Gauge32 (scan cycle in microseconds)
.2 — Process
.1.0 processTemp Gauge32 (temperature x10)
.2.0 processPressure Gauge32 (pressure x100)
.3.0 processLevel Gauge32 (level percent x10)
.3 — Counters
.1.0 totalParts Counter32
.2.0 totalRejects Counter32
.3.0 totalRunHours Counter32
.4 — Alarms
.1.0 activeAlarmCount INTEGER
.2.0 lastAlarmText STRING
.3.0 lastAlarmTime STRING (ISO 8601)

OID Tip: Always end leaf OIDs with .0 (scalar instance). Table entries use .1.N indexing. NMS tools expect this convention.


6. Application Examples

6.1 Datacenter UPS Monitoring

Monitor an APC Smart-UPS, log battery status, and trigger alarms on power events.

PROGRAM POU_UPS_Monitor
VAR
initialized : BOOL := FALSE;
ok : BOOL;
battery_status : INT;
input_voltage : INT;
output_load : INT;
ups_name : STRING;
alarm_active : BOOL := FALSE;
END_VAR

IF NOT initialized THEN
ok := SNMP_CLIENT_CREATE('ups1', '10.0.1.50', 161, 'datacenter-ro', 'v2c');
ok := SNMP_CLIENT_CONNECT('ups1');
initialized := TRUE;
RETURN;
END_IF;

IF NOT SNMP_CLIENT_IS_CONNECTED('ups1') THEN
ok := SNMP_CLIENT_CONNECT('ups1');
RETURN;
END_IF;

(* Read UPS values from poll cache — non-blocking *)
battery_status := SNMP_GET('ups1', SNMP_OID_UPS_BATTERY_STATUS);
input_voltage := SNMP_GET('ups1', SNMP_OID_UPS_INPUT_VOLTAGE);
output_load := SNMP_GET('ups1', SNMP_OID_UPS_OUTPUT_LOAD);
ups_name := SNMP_GET_SYS_NAME('ups1');

(* Battery status: 1=unknown, 2=normal, 3=low, 4=depleted *)
IF battery_status <> 2 THEN
alarm_active := TRUE;
(* Trigger plant-wide alarm via Modbus, MQTT, etc. *)
END_IF;

(* Overload protection *)
IF output_load > 80 THEN
(* Log warning — UPS load above 80% *)
END_IF;

END_PROGRAM

6.2 PDU Outlet Control

Control APC PDU outlets via SNMP SET to remotely power-cycle equipment.

PROGRAM POU_PDU_Control
VAR
initialized : BOOL := FALSE;
ok : BOOL;
outlet_state : INT;
reboot_request : BOOL; (* From HMI *)
target_outlet : INT := 1; (* Outlet number *)
END_VAR

CONST
(* APC PDU rPDU2OutletSwitchedStatusOutletState *)
APC_OUTLET_STATUS := '1.3.6.1.4.1.318.1.1.26.9.2.3.1.5.1.';
(* APC PDU rPDU2OutletSwitchedControlCommand *)
APC_OUTLET_CMD := '1.3.6.1.4.1.318.1.1.26.9.2.4.1.5.1.';
(* Commands: 1=immediateOn, 2=immediateOff, 3=immediateReboot *)
END_CONST

IF NOT initialized THEN
ok := SNMP_CLIENT_CREATE('pdu1', '10.0.1.51', 161, 'datacenter-rw', 'v2c');
ok := SNMP_CLIENT_CONNECT('pdu1');
initialized := TRUE;
RETURN;
END_IF;

(* Read outlet status *)
outlet_state := SNMP_GET('pdu1', CONCAT(APC_OUTLET_STATUS, INT_TO_STRING(target_outlet)));
(* 1=on, 2=off *)

(* HMI-triggered reboot *)
IF reboot_request THEN
ok := SNMP_SET('pdu1',
CONCAT(APC_OUTLET_CMD, INT_TO_STRING(target_outlet)),
'Integer', 3); (* 3 = immediateReboot *)
reboot_request := FALSE;
END_IF;

END_PROGRAM

6.3 Network Switch Interface Monitoring

Walk the interface table to detect link-down conditions.

PROGRAM POU_Switch_Monitor
VAR
initialized : BOOL := FALSE;
ok : BOOL;
interfaces : ARRAY[0..99] OF STRING;
walk_result : ARRAY[0..999] OF STRING; (* []MAP from walk *)
walk_timer : TON;
link_down_count : INT := 0;
END_VAR

CONST
(* ifOperStatus: 1=up, 2=down, 3=testing *)
IF_OPER_STATUS := '1.3.6.1.2.1.2.2.1.8';
END_CONST

IF NOT initialized THEN
ok := SNMP_CLIENT_CREATE('switch1', '10.0.1.1', 161, 'monitoring-ro', 'v2c');
ok := SNMP_CLIENT_CONNECT('switch1');
initialized := TRUE;
END_IF;

(* Walk interface status every 30 seconds — not every scan *)
walk_timer(IN := TRUE, PT := T#30s);
IF walk_timer.Q THEN
walk_timer(IN := FALSE);

walk_result := SNMP_WALK('switch1', IF_OPER_STATUS);

link_down_count := 0;
FOR i := 0 TO UPPER_BOUND(walk_result) DO
IF walk_result[i].value = 2 THEN
link_down_count := link_down_count + 1;
END_IF;
END_FOR;
END_IF;

END_PROGRAM

6.4 SNMPv3 Secure Monitoring

Poll a managed switch using authenticated and encrypted SNMPv3.

PROGRAM POU_SNMPv3_Monitor
VAR
initialized : BOOL := FALSE;
ok : BOOL;
sys_descr : STRING;
sys_uptime : DINT;
if_count : INT;
END_VAR

IF NOT initialized THEN
(* Create v3 client with SHA auth + AES privacy *)
ok := SNMP_CLIENT_CREATE_V3('core_switch', '10.0.1.1',
'goplc_monitor', (* USM user — must exist on the switch *)
'SHA', (* auth protocol *)
'MyAuthPhrase99!', (* auth passphrase *)
'AES', (* privacy protocol *)
'MyPrivPhrase88!'); (* privacy passphrase *)

ok := SNMP_CLIENT_CONNECT('core_switch');
initialized := TRUE;
RETURN;
END_IF;

(* Same read functions work regardless of SNMP version *)
sys_descr := SNMP_GET_SYS_DESCR('core_switch');
sys_uptime := SNMP_GET_SYS_UPTIME('core_switch');
if_count := SNMP_GET('core_switch', SNMP_OID_IF_NUMBER);

END_PROGRAM

Switch-Side Config (Cisco IOS example):

snmp-server group CONTROLFORGE_GROUP v3 priv
snmp-server user goplc_monitor CONTROLFORGE_GROUP v3 auth sha MyAuthPhrase99! priv aes 128 MyPrivPhrase88!

6.5 Trap-Driven Alarm Handling

Receive SNMP traps from UPS and switches, classify them, and route to the alarm system.

PROGRAM POU_Trap_Handler
VAR
initialized : BOOL := FALSE;
ok : BOOL;
traps : ARRAY[0..99] OF STRING; (* []MAP *)
trap_count : INT;
i : INT;
alarm_level : INT;
END_VAR

CONST
(* APC UPS enterprise OID *)
APC_ENTERPRISE := '1.3.6.1.4.1.318';
(* Common generic trap types *)
TRAP_LINK_DOWN := 2;
TRAP_LINK_UP := 3;
TRAP_ENTERPRISE := 6; (* enterprise-specific *)
END_CONST

IF NOT initialized THEN
ok := SNMP_TRAP_START('dc_traps', 1162, 'datacenter-ro,monitoring-rw');
initialized := TRUE;
RETURN;
END_IF;

(* Check for new traps every scan *)
trap_count := SNMP_TRAP_GET_COUNT();
IF trap_count = 0 THEN
RETURN;
END_IF;

(* Drain the buffer *)
traps := SNMP_TRAP_GET_BUFFER();

FOR i := 0 TO trap_count - 1 DO
(* Classify by generic trap type *)
CASE traps[i].generic_trap OF
2: (* linkDown *)
alarm_level := 2; (* Warning *)
(* Log: interface down on traps[i].source *)

3: (* linkUp *)
alarm_level := 0; (* Clear *)
(* Log: interface restored on traps[i].source *)

6: (* Enterprise-specific *)
IF traps[i].enterprise = APC_ENTERPRISE THEN
(* APC-specific trap — check specific_trap code *)
CASE traps[i].specific_trap OF
1: alarm_level := 3; (* UPS on battery — Critical *)
2: alarm_level := 0; (* UPS back on line — Clear *)
3: alarm_level := 3; (* UPS low battery — Critical *)
END_CASE;
END_IF;
END_CASE;
END_FOR;

END_PROGRAM

6.6 Exposing PLC Data via SNMP Agent

Make ControlForge process data visible to Nagios, Zabbix, or any NMS.

PROGRAM POU_SNMP_Agent
VAR
initialized : BOOL := FALSE;
ok : BOOL;
(* Process values — updated by other programs *)
tank_temp : REAL;
tank_level : REAL;
production_count : DINT;
reject_count : DINT;
machine_state : INT;
alarm_text : STRING;
END_VAR

CONST
PEN := '1.3.6.1.4.1.99999'; (* Your IANA Private Enterprise Number *)
END_CONST

IF NOT initialized THEN
ok := SNMP_AGENT_CREATE('plc_agent', 1161, 'monitoring-ro',
'ControlForge SNMP Agent - Plant Floor PLC', 'PLC-LINE1');
ok := SNMP_AGENT_START('plc_agent');
initialized := TRUE;
END_IF;

(* Update OIDs every scan — agent serves latest values *)
SNMP_AGENT_SET_INT('plc_agent', CONCAT(PEN, '.1.1.0'), machine_state);
SNMP_AGENT_SET_STR('plc_agent', CONCAT(PEN, '.1.2.0'), 'v1.0.533');
SNMP_AGENT_SET_GAUGE('plc_agent', CONCAT(PEN, '.2.1.0'), REAL_TO_INT(tank_temp * 10.0));
SNMP_AGENT_SET_GAUGE('plc_agent', CONCAT(PEN, '.2.2.0'), REAL_TO_INT(tank_level * 10.0));
SNMP_AGENT_SET_COUNTER('plc_agent', CONCAT(PEN, '.3.1.0'), production_count);
SNMP_AGENT_SET_COUNTER('plc_agent', CONCAT(PEN, '.3.2.0'), reject_count);
SNMP_AGENT_SET_STR('plc_agent', CONCAT(PEN, '.4.1.0'), alarm_text);

END_PROGRAM

Nagios check command:

# Check machine state (expect 1=Running)
check_snmp -H 10.0.0.196 -p 1161 -C monitoring-ro -o 1.3.6.1.4.1.99999.1.1.0 -w 1:1 -c 0:0

# Check tank temperature (warn >800 = 80.0C, crit >900 = 90.0C)
check_snmp -H 10.0.0.196 -p 1161 -C monitoring-ro -o 1.3.6.1.4.1.99999.2.1.0 -w :800 -c :900

6.7 Combined: Full Datacenter Monitoring Stack

A single ControlForge program that monitors UPS + PDU, receives traps, and serves aggregated status to NMS.

PROGRAM POU_DC_Monitor
VAR
initialized : BOOL := FALSE;
ok : BOOL;
(* UPS readings *)
ups_battery : INT;
ups_voltage : INT;
ups_load : INT;
(* PDU readings *)
pdu_total_amps : INT;
(* Trap processing *)
trap_count : INT;
traps : ARRAY[0..99] OF STRING;
(* Aggregated status *)
dc_health : INT := 1; (* 1=OK, 2=Warning, 3=Critical *)
alarm_msg : STRING := 'All systems normal';
END_VAR

IF NOT initialized THEN
(* Client: poll UPS and PDU *)
ok := SNMP_CLIENT_CREATE('ups1', '10.0.1.50', 161, 'datacenter-ro', 'v2c');
ok := SNMP_CLIENT_CONNECT('ups1');
ok := SNMP_CLIENT_CREATE('pdu1', '10.0.1.51', 161, 'datacenter-ro', 'v2c');
ok := SNMP_CLIENT_CONNECT('pdu1');

(* Trap receiver: catch async alerts *)
ok := SNMP_TRAP_START('dc_traps', 1162);

(* Agent: serve aggregated status to NMS *)
ok := SNMP_AGENT_CREATE('dc_agent', 1161, 'monitoring-ro',
'ControlForge DC Monitor', 'DC-MONITOR-1');
ok := SNMP_AGENT_START('dc_agent');

initialized := TRUE;
RETURN;
END_IF;

(* ---- Read UPS ---- *)
ups_battery := SNMP_GET('ups1', SNMP_OID_UPS_BATTERY_STATUS);
ups_voltage := SNMP_GET('ups1', SNMP_OID_UPS_INPUT_VOLTAGE);
ups_load := SNMP_GET('ups1', SNMP_OID_UPS_OUTPUT_LOAD);

(* ---- Read PDU ---- *)
pdu_total_amps := SNMP_GET('pdu1', '1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.1');

(* ---- Process traps ---- *)
trap_count := SNMP_TRAP_GET_COUNT();
IF trap_count > 0 THEN
traps := SNMP_TRAP_GET_BUFFER();
(* Classify and escalate — see Example 6.5 *)
END_IF;

(* ---- Compute health ---- *)
dc_health := 1;
alarm_msg := 'All systems normal';

IF ups_battery = 3 THEN (* Low battery *)
dc_health := 3;
alarm_msg := 'UPS BATTERY LOW';
ELSIF ups_battery <> 2 THEN (* Not normal *)
dc_health := 2;
alarm_msg := 'UPS battery abnormal';
END_IF;

IF ups_load > 90 THEN
dc_health := 3;
alarm_msg := 'UPS OVERLOAD >90%';
ELSIF ups_load > 80 THEN
IF dc_health < 2 THEN dc_health := 2; END_IF;
alarm_msg := 'UPS load warning >80%';
END_IF;

(* ---- Expose to NMS ---- *)
SNMP_AGENT_SET_INT('dc_agent', '1.3.6.1.4.1.99999.1.1.0', dc_health);
SNMP_AGENT_SET_STR('dc_agent', '1.3.6.1.4.1.99999.1.2.0', alarm_msg);
SNMP_AGENT_SET_GAUGE('dc_agent', '1.3.6.1.4.1.99999.2.1.0', ups_voltage);
SNMP_AGENT_SET_GAUGE('dc_agent', '1.3.6.1.4.1.99999.2.2.0', ups_load);
SNMP_AGENT_SET_GAUGE('dc_agent', '1.3.6.1.4.1.99999.2.3.0', pdu_total_amps);
SNMP_AGENT_SET_COUNTER('dc_agent', '1.3.6.1.4.1.99999.3.1.0', trap_count);

END_PROGRAM

7. Quick Reference

Client Functions

FunctionSignatureReturns
SNMP_CLIENT_CREATE(name, host [, port] [, community] [, version])BOOL
SNMP_CLIENT_CREATE_V3(name, host, user, authProto, authPass, privProto, privPass)BOOL
SNMP_CLIENT_CONNECT(name)BOOL
SNMP_CLIENT_DISCONNECT(name)BOOL
SNMP_CLIENT_IS_CONNECTED(name)BOOL
SNMP_GET(name, oidStr)ANY
SNMP_GET_MULTIPLE(name, oidStrs)MAP
SNMP_GET_NEXT(name, oidStr)MAP
SNMP_SET(name, oidStr, valueType, value)BOOL
SNMP_WALK(name, rootOidStr)[]MAP
SNMP_GET_SYS_DESCR(name)STRING
SNMP_GET_SYS_NAME(name)STRING
SNMP_GET_SYS_UPTIME(name)DINT
SNMP_GET_SYS_LOCATION(name)STRING
SNMP_GET_SYS_CONTACT(name)STRING
SNMP_CLIENT_GET_STATS(name)MAP
SNMP_CLIENT_DELETE(name)BOOL
SNMP_CLIENT_LIST()LIST

Trap Receiver Functions

FunctionSignatureReturns
SNMP_TRAP_START(name, port [, communities])BOOL
SNMP_TRAP_STOP(name)BOOL
SNMP_TRAP_IS_RUNNING(name)BOOL
SNMP_TRAP_GET_STATS(name)MAP
SNMP_TRAP_GET_BUFFER(name)[]MAP
SNMP_TRAP_GET_COUNT(name)INT
SNMP_TRAP_CLEAR_BUFFER(name)

Agent Functions

FunctionSignatureReturns
SNMP_AGENT_CREATE(name, port [, community] [, sysDescr] [, sysName])BOOL
SNMP_AGENT_START(name)BOOL
SNMP_AGENT_STOP(name)BOOL
SNMP_AGENT_IS_RUNNING(name)BOOL
SNMP_AGENT_SET_INT(name, oidStr, value)BOOL
SNMP_AGENT_SET_GAUGE(name, oidStr, value)BOOL
SNMP_AGENT_SET_COUNTER(name, oidStr, value)BOOL
SNMP_AGENT_SET_STR(name, oidStr, value)BOOL
SNMP_AGENT_GET_INT(name, oidStr)INT
SNMP_AGENT_DELETE(name)BOOL
SNMP_AGENT_LIST()LIST

OID Constants

ConstantOID
SNMP_OID_SYS_DESCR1.3.6.1.2.1.1.1.0
SNMP_OID_SYS_OBJECT_ID1.3.6.1.2.1.1.2.0
SNMP_OID_SYS_UPTIME1.3.6.1.2.1.1.3.0
SNMP_OID_SYS_CONTACT1.3.6.1.2.1.1.4.0
SNMP_OID_SYS_NAME1.3.6.1.2.1.1.5.0
SNMP_OID_SYS_LOCATION1.3.6.1.2.1.1.6.0
SNMP_OID_IF_NUMBER1.3.6.1.2.1.2.1.0
SNMP_OID_IF_TABLE1.3.6.1.2.1.2.2
SNMP_OID_UPS_BATTERY_STATUS1.3.6.1.2.1.33.1.2.1.0
SNMP_OID_UPS_INPUT_VOLTAGE1.3.6.1.2.1.33.1.3.3.1.3.1
SNMP_OID_UPS_OUTPUT_LOAD1.3.6.1.2.1.33.1.4.4.1.5.1

ControlForge v1.0.533 | SNMP v1/v2c/v3 Client, Trap Receiver, Agent Client: ~18 functions | Trap Receiver: 7 functions | Agent: ~11 functions