ControlForge Siemens S7 Protocol Guide
James M. Belcher Founder, JMB Technical Services LLC June 2026 | ControlForge v1.0.1064
1. Architecture Overview
ControlForge implements a complete Siemens S7 communication stack — both client and server — callable directly from IEC 61131-3 Structured Text. No external libraries, no TIA Portal add-ons, no code generation. You create connections, read/write data blocks and process image areas, and run an S7 server for testing — all with plain function calls in your ST programs.
| Role | Functions | Use Case |
|---|---|---|
| Client | S7_CLIENT_CREATE / S7_READ_DB_* / S7_WRITE_DB_* / S7_READ_I / S7_WRITE_M | Read/write DB blocks, inputs, outputs, markers on S7-300/400/1200/1500 PLCs |
| Server | S7_SERVER_CREATE / S7_SERVER_SET_DB / S7_SERVER_GET_M | Simulate an S7 PLC for TIA Portal testing, HMI development, or protocol bridging |
Both roles can run simultaneously. A single ControlForge instance can poll two S7-1500 PLCs as a client while serving data blocks to a WinCC HMI — all from the same ST program.
System Diagram
S7 Data Model
Siemens PLCs organize memory into distinct areas:
| Area | S7 Code | Access | Description |
|---|---|---|---|
| Data Blocks (DB) | 0x84 | Read/Write | User-defined data storage — the primary way to exchange structured data |
| Inputs (I / PE) | 0x81 | Read-Only* | Physical input image (sensors, switches) |
| Outputs (Q / PA) | 0x82 | Read/Write* | Physical output image (actuators, valves) |
| Markers (M / Flags) | 0x83 | Read/Write | Internal memory bits/bytes — often used for HMI exchange |
DB blocks are king: In modern S7 programming, data blocks are the standard interface between PLC and external systems. Inputs and outputs are typically mapped into DBs by the PLC program. Direct I/Q access is useful for diagnostics and simple configurations.
S7 Connection Parameters
Every S7 connection requires rack and slot numbers that identify which CPU to talk to:
| PLC Family | Rack | Slot | Notes |
|---|---|---|---|
| S7-300 | 0 | 2 | CPU always in slot 2 |
| S7-400 | 0 | 2-17 | Check hardware config in STEP 7 |
| S7-1200 | 0 | 0 | Single slot, rack 0 |
| S7-1500 | 0 | 0 | Single slot, rack 0 |
S7-1200/1500 access: These PLCs require PUT/GET communication to be enabled in TIA Portal: Device configuration > Protection & Security > Connection mechanisms > Permit access with PUT/GET. Without this setting, connection attempts will be rejected.
2. Client Functions
The S7 client connects to Siemens PLCs over ISO-on-TCP (port 102) and performs typed read/write operations on data blocks and process image areas.
2.1 Connection Management
S7_CLIENT_CREATE — Create Named Connection
| Param | Type | Required | Description |
|---|---|---|---|
name | STRING | Yes | Unique connection name |
host | STRING | Yes | IP address or hostname of the S7 PLC |
rack | INT | Yes | PLC rack number |
slot | INT | Yes | PLC slot number |
port | INT | No | TCP port (default 102) |
timeout_ms | INT | No | Connection timeout in milliseconds (default 5000) |
poll_rate_ms | INT | No | Background poll interval in milliseconds (default 100) |
Returns: BOOL — TRUE if the connection was created successfully.
(* Connect to S7-1500 — rack 0, slot 0 *)
ok := S7_CLIENT_CREATE('plc1', '10.0.0.34', 0, 0);
(* Connect to S7-300 — rack 0, slot 2, custom timeout *)
ok := S7_CLIENT_CREATE('plc2', '10.0.0.35', 0, 2, 102, 3000);
(* Connect with fast polling for time-critical data *)
ok := S7_CLIENT_CREATE('plc3', '10.0.0.36', 0, 0, 102, 5000, 50);
Named connections: Every S7 client connection has a unique string name. This name is used in all subsequent calls. Create one connection per PLC — multiple connections to the same PLC waste resources and may hit the PLC's connection limit.
S7_CLIENT_CONNECT — Establish S7 Connection
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name from S7_CLIENT_CREATE |
Returns: BOOL — TRUE if connected successfully.
ok := S7_CLIENT_CONNECT('plc1');
Connection sequence: S7 connection involves three steps: TCP connect, ISO-on-TCP COTP negotiation, and S7 session setup.
S7_CLIENT_CONNECThandles all three. If any step fails, the function returns FALSE.
S7_CLIENT_DISCONNECT — Close S7 Connection
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
Returns: BOOL — TRUE if disconnected successfully.
ok := S7_CLIENT_DISCONNECT('plc1');
S7_CLIENT_IS_CONNECTED — Check Connection State
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
Returns: BOOL — TRUE if the S7 session is active.
IF NOT S7_CLIENT_IS_CONNECTED('plc1') THEN
S7_CLIENT_CONNECT('plc1');
END_IF;
S7_CLIENT_DELETE — Remove Connection
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
Returns: BOOL — TRUE if the connection was deleted.
S7_CLIENT_DISCONNECT('plc1');
ok := S7_CLIENT_DELETE('plc1');
S7_CLIENT_LIST — List All Connections
Returns: []STRING — Array of all client connection names.
clients := S7_CLIENT_LIST();
(* Returns: ['plc1', 'plc2'] *)
S7_CLIENT_GET_STATS — Connection Statistics
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
Returns: MAP — Statistics including request count, response count, error count, and poll metrics.
stats := S7_CLIENT_GET_STATS('plc1');
(* Returns: {"requests": 12450, "responses": 12448, "errors": 2,
"poll_count": 8200, "avg_poll_ms": 12} *)
Error tracking: Compare requests vs. responses to detect communication problems. A growing error count may indicate network issues, PLC CPU stop, or resource limits on the PLC.
Example: Connection Lifecycle
PROGRAM POU_S7Init
VAR
state : INT := 0;
ok : BOOL;
retry_count : INT := 0;
END_VAR
CASE state OF
0: (* Create connection to S7-1500 *)
ok := S7_CLIENT_CREATE('plc1', '10.0.0.34', 0, 0);
IF ok THEN
state := 1;
END_IF;
1: (* Connect *)
ok := S7_CLIENT_CONNECT('plc1');
IF ok THEN
retry_count := 0;
state := 10;
ELSE
retry_count := retry_count + 1;
IF retry_count > 5 THEN
state := 99; (* Fault *)
END_IF;
END_IF;
10: (* Running — read/write in other programs *)
IF NOT S7_CLIENT_IS_CONNECTED('plc1') THEN
state := 1; (* Reconnect *)
END_IF;
99: (* Fault — connection failed *)
(* Log error, wait for operator intervention *)
END_CASE;
END_PROGRAM
2.2 DB Read Functions
Data block reads are the primary way to get data from an S7 PLC. Each function reads a specific data type at a byte address within a numbered DB.
S7_READ_DB_BYTE — Read Unsigned Byte (USINT)
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset within the DB |
Returns: INT — Unsigned 8-bit value (0-255).
(* Read byte at DB10.DBB0 *)
value := S7_READ_DB_BYTE('plc1', 10, 0);
S7_READ_DB_WORD — Read Unsigned Word (UINT)
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset (must be even for word alignment) |
Returns: INT — Unsigned 16-bit value (0-65535).
(* Read word at DB10.DBW2 *)
value := S7_READ_DB_WORD('plc1', 10, 2);
S7_READ_DB_DWORD — Read Unsigned Double Word (UDINT)
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset (should be 4-byte aligned) |
Returns: DINT — Unsigned 32-bit value.
(* Read double word at DB10.DBD4 *)
value := S7_READ_DB_DWORD('plc1', 10, 4);
S7_READ_DB_INT — Read Signed Integer (INT, 16-bit)
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset |
Returns: INT — Signed 16-bit value (-32768 to 32767).
(* Read signed integer at DB10.DBW8 *)
temperature := S7_READ_DB_INT('plc1', 10, 8);
(* Returns: -15 for a below-zero temperature *)
S7_READ_DB_DINT — Read Signed Double Integer (DINT, 32-bit)
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset |
Returns: DINT — Signed 32-bit value.
(* Read signed 32-bit integer at DB10.DBD10 *)
encoder_count := S7_READ_DB_DINT('plc1', 10, 10);
(* Returns: -142857 *)
S7_READ_DB_REAL — Read Floating Point (REAL, 32-bit)
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset |
Returns: REAL — IEEE 754 single-precision float.
(* Read real at DB10.DBD14 — motor speed in RPM *)
speed := S7_READ_DB_REAL('plc1', 10, 14);
(* Returns: 1487.5 *)
Byte order: Siemens PLCs use big-endian byte order. ControlForge handles the byte-swapping automatically — you always get native values.
S7_READ_DB_BOOL — Read Single Bit
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset |
bit | INT | Bit number within the byte (0-7) |
Returns: BOOL — TRUE or FALSE.
(* Read DB10.DBX0.0 — first bit of first byte *)
motor_running := S7_READ_DB_BOOL('plc1', 10, 0, 0);
(* Read DB10.DBX0.3 — fourth bit of first byte *)
alarm_active := S7_READ_DB_BOOL('plc1', 10, 0, 3);
(* Read DB10.DBX1.7 — eighth bit of second byte *)
limit_reached := S7_READ_DB_BOOL('plc1', 10, 1, 7);
Bit addressing in S7: Bit 0 is the least significant bit.
DBX0.0is byte 0, bit 0.DBX0.7is byte 0, bit 7.DBX1.0is byte 1, bit 0. This matches the TIA Portal variable table layout exactly.
Example: Reading a Complete DB Structure
PROGRAM POU_ReadDB
VAR
(* Mapped to S7 PLC DB10 layout:
Offset 0: BOOL - motor_running (DBX0.0)
Offset 0: BOOL - fault_active (DBX0.1)
Offset 2: INT - speed_setpoint (DBW2)
Offset 4: INT - speed_actual (DBW4)
Offset 6: REAL - temperature (DBD6)
Offset 10: REAL - pressure (DBD10)
Offset 14: DINT - total_cycles (DBD14)
*)
motor_running : BOOL;
fault_active : BOOL;
speed_setpoint : INT;
speed_actual : INT;
temperature : REAL;
pressure : REAL;
total_cycles : DINT;
END_VAR
(* Read all values from DB10 *)
motor_running := S7_READ_DB_BOOL('plc1', 10, 0, 0);
fault_active := S7_READ_DB_BOOL('plc1', 10, 0, 1);
speed_setpoint := S7_READ_DB_INT('plc1', 10, 2);
speed_actual := S7_READ_DB_INT('plc1', 10, 4);
temperature := S7_READ_DB_REAL('plc1', 10, 6);
pressure := S7_READ_DB_REAL('plc1', 10, 10);
total_cycles := S7_READ_DB_DINT('plc1', 10, 14);
END_PROGRAM
2.3 DB Write Functions
Each write function mirrors its read counterpart. All return BOOL — TRUE if the write was acknowledged by the PLC.
S7_WRITE_DB_BYTE — Write Unsigned Byte
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset |
value | INT | Value to write (0-255) |
Returns: BOOL — TRUE if write succeeded.
ok := S7_WRITE_DB_BYTE('plc1', 10, 0, 128);
S7_WRITE_DB_WORD — Write Unsigned Word
ok := S7_WRITE_DB_WORD('plc1', 10, 2, 5000);
S7_WRITE_DB_DWORD — Write Unsigned Double Word
ok := S7_WRITE_DB_DWORD('plc1', 10, 4, 1000000);
S7_WRITE_DB_INT — Write Signed Integer (16-bit)
(* Write speed setpoint — signed allows negative values *)
ok := S7_WRITE_DB_INT('plc1', 10, 2, -500);
S7_WRITE_DB_DINT — Write Signed Double Integer (32-bit)
ok := S7_WRITE_DB_DINT('plc1', 10, 10, 142857);
S7_WRITE_DB_REAL — Write Floating Point
(* Write temperature setpoint *)
ok := S7_WRITE_DB_REAL('plc1', 10, 14, 72.5);
S7_WRITE_DB_BOOL — Write Single Bit
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
db | INT | Data block number |
byteAddr | INT | Byte offset |
bit | INT | Bit number (0-7) |
value | BOOL | TRUE or FALSE |
Returns: BOOL — TRUE if write succeeded.
(* Set motor run command — DB10.DBX0.0 *)
ok := S7_WRITE_DB_BOOL('plc1', 10, 0, 0, TRUE);
(* Clear alarm acknowledge — DB10.DBX0.1 *)
ok := S7_WRITE_DB_BOOL('plc1', 10, 0, 1, FALSE);
Write atomicity: Each S7_WRITE_DB call is a separate S7 protocol transaction. If you need to write multiple values atomically (e.g., a setpoint and its enable bit), write them to a staging DB and have the PLC program copy them in a single scan.
Example: Writing Commands to a PLC
PROGRAM POU_WriteDB
VAR
ok : BOOL;
speed_cmd : INT := 1500;
temp_setpoint : REAL := 72.5;
start_cmd : BOOL := FALSE;
END_VAR
(* Write command values to DB20 *)
ok := S7_WRITE_DB_INT('plc1', 20, 0, speed_cmd);
ok := S7_WRITE_DB_REAL('plc1', 20, 2, temp_setpoint);
ok := S7_WRITE_DB_BOOL('plc1', 20, 6, 0, start_cmd);
END_PROGRAM
2.4 Area Read Functions (Inputs, Outputs, Markers)
These functions read directly from the PLC's process image areas — inputs (I), outputs (Q), and markers/flags (M). Byte-level reads return arrays for reading multiple consecutive bytes.
S7_READ_I — Read Input Bytes
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
byteAddr | INT | Starting byte offset |
count | INT | Number of bytes to read |
Returns: []INT — Array of byte values (0-255 each).
(* Read 4 input bytes starting at IB0 *)
inputs := S7_READ_I('plc1', 0, 4);
(* inputs[0] = IB0, inputs[1] = IB1, inputs[2] = IB2, inputs[3] = IB3 *)
S7_READ_Q — Read Output Bytes
(* Read 2 output bytes starting at QB0 *)
outputs := S7_READ_Q('plc1', 0, 2);
S7_READ_M — Read Marker Bytes
(* Read 8 marker bytes starting at MB0 *)
markers := S7_READ_M('plc1', 0, 8);
S7_READ_I_BOOL — Read Input Bit
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
byteAddr | INT | Byte offset |
bit | INT | Bit number (0-7) |
Returns: BOOL — Input state.
(* Read I0.0 — first input bit *)
sensor := S7_READ_I_BOOL('plc1', 0, 0);
(* Read I1.5 — second byte, bit 5 *)
limit_sw := S7_READ_I_BOOL('plc1', 1, 5);
S7_READ_Q_BOOL — Read Output Bit
(* Read Q0.0 — first output bit *)
valve_state := S7_READ_Q_BOOL('plc1', 0, 0);
S7_READ_M_BOOL — Read Marker Bit
(* Read M0.0 — first marker bit *)
hmi_flag := S7_READ_M_BOOL('plc1', 0, 0);
(* Read M10.3 — commonly used for HMI handshake bits *)
ack_bit := S7_READ_M_BOOL('plc1', 10, 3);
Example: Reading Process Image
PROGRAM POU_ReadIO
VAR
(* Digital inputs *)
start_button : BOOL;
stop_button : BOOL;
e_stop : BOOL;
guard_door : BOOL;
(* Markers for HMI exchange *)
hmi_mode : INT;
marker_bytes : ARRAY[0..3] OF INT;
END_VAR
(* Read individual input bits *)
start_button := S7_READ_I_BOOL('plc1', 0, 0);
stop_button := S7_READ_I_BOOL('plc1', 0, 1);
e_stop := S7_READ_I_BOOL('plc1', 0, 2);
guard_door := S7_READ_I_BOOL('plc1', 0, 3);
(* Read marker area as bytes *)
marker_bytes := S7_READ_M('plc1', 0, 4);
END_PROGRAM
2.5 Area Write Functions (Outputs, Markers)
S7_WRITE_M — Write Marker Bytes
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
byteAddr | INT | Starting byte offset |
values | []INT | Array of byte values to write |
Returns: BOOL — TRUE if write succeeded.
(* Write 2 bytes to MB0 and MB1 *)
ok := S7_WRITE_M('plc1', 0, [255, 128]);
S7_WRITE_Q — Write Output Bytes
(* Write 1 byte to QB0 *)
ok := S7_WRITE_Q('plc1', 0, [16#FF]);
Direct output writes: Writing to the output area (Q) directly overrides the PLC program's output image. This can cause unexpected actuator behavior. Use with extreme caution — in production, write to marker or DB areas and let the PLC program control the outputs.
S7_WRITE_M_BOOL — Write Marker Bit
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
byteAddr | INT | Byte offset |
bit | INT | Bit number (0-7) |
value | BOOL | TRUE or FALSE |
Returns: BOOL — TRUE if write succeeded.
(* Set M0.0 — handshake bit to PLC *)
ok := S7_WRITE_M_BOOL('plc1', 0, 0, TRUE);
(* Clear M10.7 — reset flag *)
ok := S7_WRITE_M_BOOL('plc1', 10, 7, FALSE);
S7_WRITE_Q_BOOL — Write Output Bit
(* Set Q0.0 — first output *)
ok := S7_WRITE_Q_BOOL('plc1', 0, 0, TRUE);
2.6 Background Polling
S7_ADD_POLL — Register a Polled Data Range
Adds a memory area to the background poll list. Polled data is refreshed automatically at the rate specified in S7_CLIENT_CREATE (the poll_rate_ms parameter), so subsequent reads return cached values without blocking.
| Param | Type | Description |
|---|---|---|
name | STRING | Connection name |
area | STRING | Memory area: 'DB', 'I', 'Q', or 'M' |
dbNumber | INT | DB number (0 for I/Q/M areas) |
byteAddr | INT | Starting byte offset |
byteCount | INT | Number of bytes to poll |
Returns: BOOL — TRUE if the poll entry was added.
(* Poll DB10 bytes 0-19 in the background *)
ok := S7_ADD_POLL('plc1', 'DB', 10, 0, 20);
(* Poll input bytes 0-7 *)
ok := S7_ADD_POLL('plc1', 'I', 0, 0, 8);
(* Poll marker bytes 0-15 *)
ok := S7_ADD_POLL('plc1', 'M', 0, 0, 16);
Polling vs. on-demand reads: Without polling, each
S7_READ_DB_*call generates a network request (5-20 ms round-trip). With polling, a background goroutine refreshes the data at the configured rate, and reads return instantly from the cache. Use polling for frequently-read data; use on-demand reads for infrequent or diagnostic access.
Example: Polled Data Access
PROGRAM POU_PolledRead
VAR
state : INT := 0;
ok : BOOL;
speed : REAL;
temp : REAL;
running : BOOL;
END_VAR
CASE state OF
0: (* Setup connection and polling *)
ok := S7_CLIENT_CREATE('plc1', '10.0.0.34', 0, 0, 102, 5000, 50);
IF ok THEN state := 1; END_IF;
1: (* Connect *)
ok := S7_CLIENT_CONNECT('plc1');
IF ok THEN state := 2; END_IF;
2: (* Register poll ranges *)
S7_ADD_POLL('plc1', 'DB', 10, 0, 20);
state := 10;
10: (* Running — reads return cached polled data, zero latency *)
speed := S7_READ_DB_REAL('plc1', 10, 0);
temp := S7_READ_DB_REAL('plc1', 10, 4);
running := S7_READ_DB_BOOL('plc1', 10, 8, 0);
IF NOT S7_CLIENT_IS_CONNECTED('plc1') THEN
state := 1;
END_IF;
END_CASE;
END_PROGRAM
3. Server Functions
The S7 server emulates a Siemens PLC, accepting incoming S7 connections and exposing DB blocks, inputs, outputs, and markers. This is invaluable for testing TIA Portal projects, developing HMI screens, or acting as a protocol bridge.
3.1 Server Management
S7_SERVER_CREATE — Create Named Server
| Param | Type | Required | Description |
|---|---|---|---|
name | STRING | Yes | Unique server name |
port | INT | Yes | TCP listen port |
Returns: BOOL — TRUE if the server was created.
(* Create S7 server on the standard S7 port *)
ok := S7_SERVER_CREATE('sim', 102);
(* Create on a non-standard port to avoid permission issues *)
ok := S7_SERVER_CREATE('sim', 1102);
Port 102: The standard ISO-on-TCP port (102) may require root/admin privileges. During development, use a port above 1024. TIA Portal and WinCC can be configured to connect to non-standard ports.
S7_SERVER_START — Begin Listening
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
Returns: BOOL — TRUE if the server started listening.
ok := S7_SERVER_START('sim');
S7_SERVER_STOP — Stop Listening
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
Returns: BOOL — TRUE if the server stopped.
ok := S7_SERVER_STOP('sim');
S7_SERVER_IS_RUNNING — Check Server State
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
Returns: BOOL — TRUE if the server is actively listening.
IF NOT S7_SERVER_IS_RUNNING('sim') THEN
S7_SERVER_START('sim');
END_IF;
S7_SERVER_DELETE — Remove Server
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
Returns: BOOL — TRUE if the server was deleted.
S7_SERVER_STOP('sim');
ok := S7_SERVER_DELETE('sim');
S7_SERVER_LIST — List All Servers
Returns: []STRING — Array of all server names.
servers := S7_SERVER_LIST();
(* Returns: ['sim'] *)
3.2 DB Area Access
S7_SERVER_SET_DB — Write to Server DB Area
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
db | INT | Data block number |
byteAddr | INT | Starting byte offset |
values | []INT | Array of byte values to write |
Returns: BOOL — TRUE if the value was set.
(* Write 4 bytes to DB10 starting at offset 0 *)
ok := S7_SERVER_SET_DB('sim', 10, 0, [16#00, 16#FF, 16#12, 16#34]);
(* Pre-populate a REAL value (72.5 = 42 91 00 00 in IEEE 754 big-endian) *)
ok := S7_SERVER_SET_DB('sim', 10, 4, [16#42, 16#91, 16#00, 16#00]);
S7_SERVER_GET_DB — Read from Server DB Area
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
db | INT | Data block number |
byteAddr | INT | Byte offset to read |
Returns: INT — the single byte at byteAddr.
Reads are one byte at a time. Unlike
S7_SERVER_SET_DB, which takes an array, the getters have nocountargument — loop for a range. A block-read form returning an array is on the deferred list inTODO.md.
(* Read 10 bytes from DB10 *)
FOR i := 0 TO 9 DO
data[i] := S7_SERVER_GET_DB('sim', 10, i);
END_FOR;
Server DB storage: The server automatically allocates DB storage on first access. You don't need to pre-define DB sizes — just write to any DB number and offset.
3.3 Marker Area Access
S7_SERVER_SET_M — Write to Server Marker Area
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
byteAddr | INT | Starting byte offset |
values | []INT | Array of byte values |
Returns: BOOL — TRUE if the value was set.
(* Set MB0 = 0xFF, MB1 = 0x00 *)
ok := S7_SERVER_SET_M('sim', 0, [16#FF, 16#00]);
S7_SERVER_GET_M — Read from Server Marker Area
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
byteAddr | INT | Byte offset to read |
Returns: INT — the single byte at byteAddr.
(* Read MB0..MB3 *)
FOR i := 0 TO 3 DO
markers[i] := S7_SERVER_GET_M('sim', i);
END_FOR;
3.4 Input/Output Area Access
S7_SERVER_SET_I — Write to Server Input Area
| Param | Type | Description |
|---|---|---|
name | STRING | Server name |
byteAddr | INT | Starting byte offset |
values | []INT | Array of byte values |
Returns: BOOL — TRUE if the value was set.
(* Simulate input byte IB0 with all bits set *)
ok := S7_SERVER_SET_I('sim', 0, [16#FF]);
S7_SERVER_GET_I — Read from Server Input Area
(* One byte per call — read IB0 *)
inputs := S7_SERVER_GET_I('sim', 0);
S7_SERVER_SET_Q — Write to Server Output Area
ok := S7_SERVER_SET_Q('sim', 0, [16#A5]);
S7_SERVER_GET_Q — Read from Server Output Area
(* One byte per call — read QB0 *)
outputs := S7_SERVER_GET_Q('sim', 0);
Server areas as simulation: Use
S7_SERVER_SET_Ito simulate sensor inputs for TIA Portal programs. UseS7_SERVER_GET_Qto verify that the PLC program drives the correct outputs. This creates a hardware-in-the-loop test environment without physical I/O.
Example: Server Lifecycle
PROGRAM POU_S7Server
VAR
state : INT := 0;
ok : BOOL;
scan_count : DINT := 0;
END_VAR
CASE state OF
0: (* Create server *)
ok := S7_SERVER_CREATE('sim', 1102);
IF ok THEN
state := 1;
END_IF;
1: (* Start listening *)
ok := S7_SERVER_START('sim');
IF ok THEN
state := 2;
END_IF;
2: (* Pre-populate data blocks *)
S7_SERVER_SET_DB('sim', 10, 0, [0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
0, 0, 0, 0, 0, 0, 0, 0, 0, 0]);
state := 10;
10: (* Running — update simulated data *)
scan_count := scan_count + 1;
(* Simulate changing process values *)
S7_SERVER_SET_DB('sim', 10, 0, [DINT_TO_INT(scan_count MOD 256)]);
IF NOT S7_SERVER_IS_RUNNING('sim') THEN
state := 1;
END_IF;
END_CASE;
END_PROGRAM
4. Complete Example: Reading Process Data from an S7-1500
This example connects to an S7-1500 PLC running a packaging line, reads process data from DB10, and writes setpoints to DB20. The DB layout matches a typical TIA Portal project structure.
PLC DB Layout
| DB | Offset | Type | Variable | Description |
|---|---|---|---|---|
| DB10 | 0.0 | BOOL | line_running | Line status |
| DB10 | 0.1 | BOOL | fault_active | Active fault |
| DB10 | 0.2 | BOOL | infeed_ready | Infeed conveyor ready |
| DB10 | 2 | INT | line_speed | Actual speed (packages/min) |
| DB10 | 4 | INT | reject_count | Rejected packages |
| DB10 | 6 | REAL | temperature | Seal bar temperature (deg C) |
| DB10 | 10 | REAL | pressure | Vacuum pressure (mbar) |
| DB10 | 14 | DINT | total_count | Total packages since reset |
| DB20 | 0.0 | BOOL | start_cmd | Start command |
| DB20 | 0.1 | BOOL | stop_cmd | Stop command |
| DB20 | 2 | INT | speed_setpoint | Speed setpoint (packages/min) |
| DB20 | 4 | REAL | temp_setpoint | Temperature setpoint (deg C) |
PROGRAM POU_PackagingLine
VAR
(* Connection state *)
state : INT := 0;
ok : BOOL;
retry_count : INT := 0;
(* Process data from DB10 *)
line_running : BOOL;
fault_active : BOOL;
infeed_ready : BOOL;
line_speed : INT;
reject_count : INT;
temperature : REAL;
pressure : REAL;
total_count : DINT;
(* Commands to DB20 *)
start_cmd : BOOL := FALSE;
stop_cmd : BOOL := FALSE;
speed_setpoint : INT := 120;
temp_setpoint : REAL := 185.0;
END_VAR
CASE state OF
0: (* Create connection to S7-1500 *)
ok := S7_CLIENT_CREATE('pack_plc', '10.0.0.34', 0, 0);
IF ok THEN
state := 1;
END_IF;
1: (* Connect *)
ok := S7_CLIENT_CONNECT('pack_plc');
IF ok THEN
retry_count := 0;
state := 2;
ELSE
retry_count := retry_count + 1;
IF retry_count > 5 THEN
state := 99;
END_IF;
END_IF;
2: (* Register poll for fast reads *)
S7_ADD_POLL('pack_plc', 'DB', 10, 0, 18);
state := 10;
10: (* Running — read process data *)
IF NOT S7_CLIENT_IS_CONNECTED('pack_plc') THEN
state := 1;
END_IF;
(* Read DB10 — status and feedback *)
line_running := S7_READ_DB_BOOL('pack_plc', 10, 0, 0);
fault_active := S7_READ_DB_BOOL('pack_plc', 10, 0, 1);
infeed_ready := S7_READ_DB_BOOL('pack_plc', 10, 0, 2);
line_speed := S7_READ_DB_INT('pack_plc', 10, 2);
reject_count := S7_READ_DB_INT('pack_plc', 10, 4);
temperature := S7_READ_DB_REAL('pack_plc', 10, 6);
pressure := S7_READ_DB_REAL('pack_plc', 10, 10);
total_count := S7_READ_DB_DINT('pack_plc', 10, 14);
state := 11;
11: (* Write commands to DB20 *)
ok := S7_WRITE_DB_BOOL('pack_plc', 20, 0, 0, start_cmd);
ok := S7_WRITE_DB_BOOL('pack_plc', 20, 0, 1, stop_cmd);
ok := S7_WRITE_DB_INT('pack_plc', 20, 2, speed_setpoint);
ok := S7_WRITE_DB_REAL('pack_plc', 20, 4, temp_setpoint);
(* Auto-clear one-shot commands *)
start_cmd := FALSE;
stop_cmd := FALSE;
state := 10; (* Loop back to read *)
99: (* Fault *)
(* Log error, wait for intervention *)
END_CASE;
END_PROGRAM
DB access optimization: The S7 protocol allows reading up to 480 bytes per PDU (negotiated at connection time). Grouping reads within a single DB range via
S7_ADD_POLLis far more efficient than individual typed reads. The background poll fetches all 18 bytes of DB10 in a single S7 transaction, and the typed read functions extract values from the cache.
5. Complete Example: S7 Server for TIA Portal Testing
This example creates an S7 server that simulates the packaging line PLC from Section 4. A TIA Portal project can connect to this server for HMI development and logic testing without the physical PLC.
PROGRAM POU_S7Simulator
VAR
(* Server state *)
state : INT := 0;
ok : BOOL;
scan_count : DINT := 0;
(* Simulated process values *)
sim_running : BOOL := FALSE;
sim_speed : INT := 0;
sim_temp : REAL := 25.0;
sim_pressure : REAL := 1013.0;
sim_total : DINT := 0;
(* Commands received from TIA Portal / HMI *)
cmd_byte : INT;
start_received : BOOL;
stop_received : BOOL;
END_VAR
CASE state OF
0: (* Create and start server *)
ok := S7_SERVER_CREATE('sim', 1102);
IF ok THEN state := 1; END_IF;
1:
ok := S7_SERVER_START('sim');
IF ok THEN state := 2; END_IF;
2: (* Initialize DB10 with zeros *)
S7_SERVER_SET_DB('sim', 10, 0, [0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
0, 0, 0, 0, 0, 0, 0, 0]);
S7_SERVER_SET_DB('sim', 20, 0, [0, 0, 0, 0, 0, 0, 0, 0]);
state := 10;
10: (* Running — update simulation every scan *)
scan_count := scan_count + 1;
(* Read commands from DB20 (written by TIA Portal / HMI).
Only byte 0 carries the command bits, so read that one byte. *)
cmd_byte := S7_SERVER_GET_DB('sim', 20, 0);
start_received := (cmd_byte AND 1) = 1; (* Bit 0.0 *)
stop_received := (cmd_byte AND 2) = 2; (* Bit 0.1 *)
(* Process commands *)
IF start_received AND NOT sim_running THEN
sim_running := TRUE;
END_IF;
IF stop_received THEN
sim_running := FALSE;
END_IF;
(* Simulate process behavior *)
IF sim_running THEN
sim_speed := 120;
sim_temp := sim_temp + 0.1;
IF sim_temp > 190.0 THEN sim_temp := 185.0; END_IF;
sim_pressure := 950.0;
sim_total := sim_total + 1;
ELSE
sim_speed := 0;
sim_temp := sim_temp - 0.05;
IF sim_temp < 25.0 THEN sim_temp := 25.0; END_IF;
sim_pressure := 1013.0;
END_IF;
(* Write simulated status to DB10 *)
(* Byte 0: status bits *)
S7_SERVER_SET_DB('sim', 10, 0, [BOOL_TO_INT(sim_running)]);
(* Bytes 2-3: line speed as INT (big-endian) *)
S7_SERVER_SET_DB('sim', 10, 2, [sim_speed / 256, sim_speed MOD 256]);
(* Note: REAL and DINT values require IEEE 754 / big-endian
byte packing. In practice, use helper functions or
write complete byte arrays from your simulation model. *)
IF NOT S7_SERVER_IS_RUNNING('sim') THEN
state := 1;
END_IF;
END_CASE;
END_PROGRAM
TIA Portal connection: In TIA Portal, add an "Unspecified S7 300/400" as a connection partner and configure the IP address and port of the ControlForge server. The S7 server responds to standard S7comm read/write requests — TIA Portal and WinCC treat it like a real PLC.
6. Gateway Example: S7 to MQTT Bridge
This example reads data from an S7-1500 PLC and publishes it to an MQTT broker, bridging the OT (Siemens) and IT (MQTT/JSON) worlds.
PROGRAM POU_S7_MQTT_Gateway
VAR
(* State machine *)
state : INT := 0;
ok : BOOL;
scan_count : DINT := 0;
publish_interval : DINT := 10;
(* S7 data *)
speed : REAL;
temp : REAL;
pressure : REAL;
running : BOOL;
(* MQTT *)
payload : STRING;
END_VAR
CASE state OF
0: (* Initialize S7 client *)
ok := S7_CLIENT_CREATE('plc', '10.0.0.34', 0, 0);
IF ok THEN state := 1; END_IF;
1: (* Connect S7 *)
ok := S7_CLIENT_CONNECT('plc');
IF ok THEN state := 2; END_IF;
2: (* Initialize MQTT *)
ok := MQTT_CLIENT_CREATE('gw', 'tcp://10.0.0.144:1883', 'cf-gw');
IF ok THEN
ok := MQTT_CONNECT('gw');
IF ok THEN state := 3; END_IF;
END_IF;
3: (* Register polling *)
S7_ADD_POLL('plc', 'DB', 10, 0, 20);
state := 10;
10: (* Running — read and publish *)
scan_count := scan_count + 1;
IF NOT S7_CLIENT_IS_CONNECTED('plc') THEN
S7_CLIENT_CONNECT('plc');
END_IF;
(* Read from polled cache *)
speed := S7_READ_DB_REAL('plc', 10, 0);
temp := S7_READ_DB_REAL('plc', 10, 4);
pressure := S7_READ_DB_REAL('plc', 10, 8);
running := S7_READ_DB_BOOL('plc', 10, 12, 0);
(* Publish at reduced rate *)
IF (scan_count MOD publish_interval) = 0 THEN
payload := CONCAT('{"speed":', REAL_TO_STRING(speed),
',"temp":', REAL_TO_STRING(temp),
',"pressure":', REAL_TO_STRING(pressure),
',"running":', BOOL_TO_STRING(running), '}');
MQTT_PUBLISH('gw', 'plant/line1/data', payload);
END_IF;
(* Publish connection stats periodically *)
IF (scan_count MOD 100) = 0 THEN
MQTT_PUBLISH('gw', 'plant/line1/stats',
S7_CLIENT_GET_STATS('plc'));
END_IF;
END_CASE;
END_PROGRAM
7. Advanced Patterns
7.1 Multi-PLC Polling
PROGRAM POU_MultiPLC
VAR
poll_index : INT := 0;
plcs : ARRAY[0..2] OF STRING := ['plc_line1', 'plc_line2', 'plc_line3'];
speed : REAL;
END_VAR
(* Round-robin: read one PLC per scan to distribute load *)
speed := S7_READ_DB_REAL(plcs[poll_index], 10, 0);
poll_index := poll_index + 1;
IF poll_index > 2 THEN
poll_index := 0;
END_IF;
END_PROGRAM
Why round-robin? Each S7 read blocks for the round-trip time (5-30 ms on a local network). Reading from three PLCs sequentially every scan adds 15-90 ms. With background polling enabled via
S7_ADD_POLL, the round-robin pattern is less critical since reads return from cache — but it remains useful for write operations that cannot be cached.
7.2 Dual Role: Client and Server Simultaneously
PROGRAM POU_DualRole
VAR
state : INT := 0;
ok : BOOL;
speed : REAL;
temp : REAL;
i : INT;
mirror_buf : ARRAY[0..19] OF INT;
END_VAR
CASE state OF
0: (* Initialize both roles *)
ok := S7_CLIENT_CREATE('plc', '10.0.0.34', 0, 0);
ok := S7_SERVER_CREATE('mirror', 1102);
IF ok THEN state := 1; END_IF;
1: (* Connect/Start *)
S7_CLIENT_CONNECT('plc');
S7_SERVER_START('mirror');
S7_ADD_POLL('plc', 'DB', 10, 0, 20);
state := 10;
10: (* Running — mirror PLC data to server *)
(* Read from real PLC *)
speed := S7_READ_DB_REAL('plc', 10, 0);
temp := S7_READ_DB_REAL('plc', 10, 4);
(* Mirror to server DB for HMI/SCADA access *)
(* Write raw bytes — REAL as IEEE 754 big-endian.
SET takes an array; GET returns one byte, so build the array. *)
FOR i := 0 TO 19 DO
mirror_buf[i] := S7_SERVER_GET_DB('mirror', 10, i);
END_FOR;
S7_SERVER_SET_DB('mirror', 10, 0, mirror_buf);
(* Alternatively, forward entire DB block from client reads *)
END_CASE;
END_PROGRAM
7.3 Cross-Protocol Bridge: Modbus TCP to S7
PROGRAM POU_Modbus_S7_Bridge
VAR
state : INT := 0;
ok : BOOL;
regs : ARRAY[0..9] OF INT;
END_VAR
CASE state OF
0: (* Initialize both protocols *)
ok := MB_CLIENT_CREATE('vfd', '10.0.0.50', 502, 1);
ok := S7_CLIENT_CREATE('plc', '10.0.0.34', 0, 0);
IF ok THEN state := 1; END_IF;
1: (* Connect both *)
MB_CLIENT_CONNECT('vfd');
S7_CLIENT_CONNECT('plc');
state := 10;
10: (* Running — bridge Modbus VFD data into S7 PLC DB *)
(* Read VFD status over Modbus *)
regs := MB_READ_HOLDING('vfd', 0, 5);
(* Write to S7 PLC DB30 as INT values *)
ok := S7_WRITE_DB_INT('plc', 30, 0, regs[0]); (* Output freq *)
ok := S7_WRITE_DB_INT('plc', 30, 2, regs[1]); (* Current *)
ok := S7_WRITE_DB_INT('plc', 30, 4, regs[2]); (* Voltage *)
ok := S7_WRITE_DB_INT('plc', 30, 6, regs[3]); (* Status word *)
ok := S7_WRITE_DB_INT('plc', 30, 8, regs[4]); (* Fault code *)
(* Read speed command from S7 PLC, forward to VFD *)
ok := MB_WRITE_REGISTER('vfd', 8192,
S7_READ_DB_INT('plc', 30, 10));
END_CASE;
END_PROGRAM
Protocol bridging: ControlForge acts as a universal translator. The S7 PLC program reads VFD data from its DB30 as if it were local data — it doesn't know or care that the values originate from a Modbus device. This decouples the PLC program from the field protocol.
8. PLC Family Notes
S7-300 / S7-400
- Rack/Slot: Typically rack 0, slot 2. Check STEP 7 hardware configuration for multi-rack setups.
- No special configuration required. PUT/GET is enabled by default on 300/400 series.
- Connection limits: S7-300 supports 12-32 concurrent connections depending on CPU model. S7-400 supports up to 64.
- DB access: Standard (non-optimized) DB blocks only. These PLCs do not support optimized block access.
S7-1200
- Rack/Slot: Always rack 0, slot 0.
- PUT/GET must be enabled in TIA Portal: Device configuration > Protection & Security > Connection mechanisms > Permit access with PUT/GET communication.
- DB blocks must be non-optimized: In TIA Portal, open the DB properties and uncheck Optimized block access. Optimized DBs use internal addressing that external clients cannot access.
- Connection limit: 8 concurrent connections (CPU firmware dependent).
- Firmware: Requires firmware V4.0 or later for full PUT/GET support.
S7-1500
- Rack/Slot: Always rack 0, slot 0.
- PUT/GET must be enabled — same TIA Portal setting as S7-1200.
- DB blocks must be non-optimized for external access. Alternatively, use a dedicated "interface DB" with optimized access disabled while keeping internal DBs optimized.
- Connection limit: Up to 32 concurrent connections depending on CPU model.
- Security: S7-1500 supports access levels (full access, read access, HMI access, no access). Ensure the access level permits PUT/GET.
Optimized vs. standard DB access: TIA Portal defaults to "optimized block access" for S7-1200/1500 DBs. This reorders variables internally for performance, breaking external byte-offset addressing. For any DB that ControlForge will read/write, disable optimized access. A common pattern is to create dedicated "exchange DBs" (e.g., DB10 for status, DB20 for commands) with optimized access disabled, and use optimized DBs for internal PLC logic.
Appendix A: S7 Address Mapping Quick Reference
| TIA Portal Address | ControlForge Function | Parameters |
|---|---|---|
DB10.DBX0.0 | S7_READ_DB_BOOL('c', 10, 0, 0) | db=10, byte=0, bit=0 |
DB10.DBX0.7 | S7_READ_DB_BOOL('c', 10, 0, 7) | db=10, byte=0, bit=7 |
DB10.DBX1.0 | S7_READ_DB_BOOL('c', 10, 1, 0) | db=10, byte=1, bit=0 |
DB10.DBB0 | S7_READ_DB_BYTE('c', 10, 0) | db=10, byte=0 |
DB10.DBW2 | S7_READ_DB_WORD('c', 10, 2) | db=10, byte=2 |
DB10.DBD4 | S7_READ_DB_DWORD('c', 10, 4) | db=10, byte=4 |
DB10.DBD4 (REAL) | S7_READ_DB_REAL('c', 10, 4) | db=10, byte=4 |
I0.0 | S7_READ_I_BOOL('c', 0, 0) | byte=0, bit=0 |
IB0 (byte) | S7_READ_I('c', 0, 1) | byte=0, count=1 |
Q0.0 | S7_READ_Q_BOOL('c', 0, 0) | byte=0, bit=0 |
M10.3 | S7_READ_M_BOOL('c', 10, 3) | byte=10, bit=3 |
MB0-MB7 | S7_READ_M('c', 0, 8) | byte=0, count=8 |
Appendix B: Quick Reference — All Functions
Client Functions (~24)
| Function | Returns | Description |
|---|---|---|
S7_CLIENT_CREATE(name, host, rack, slot [, port] [, timeout_ms] [, poll_rate_ms]) | BOOL | Create named connection |
S7_CLIENT_CONNECT(name) | BOOL | Establish S7 connection |
S7_CLIENT_DISCONNECT(name) | BOOL | Close S7 connection |
S7_CLIENT_IS_CONNECTED(name) | BOOL | Check connection state |
S7_CLIENT_DELETE(name) | BOOL | Remove connection |
S7_CLIENT_LIST() | []STRING | List all connections |
S7_CLIENT_GET_STATS(name) | MAP | Request/response/error/poll counts |
S7_READ_DB_BYTE(name, db, byteAddr) | INT | Read unsigned byte (USINT) |
S7_READ_DB_WORD(name, db, byteAddr) | INT | Read unsigned word (UINT) |
S7_READ_DB_DWORD(name, db, byteAddr) | DINT | Read unsigned double word (UDINT) |
S7_READ_DB_INT(name, db, byteAddr) | INT | Read signed 16-bit integer |
S7_READ_DB_DINT(name, db, byteAddr) | DINT | Read signed 32-bit integer |
S7_READ_DB_REAL(name, db, byteAddr) | REAL | Read 32-bit float (IEEE 754) |
S7_READ_DB_BOOL(name, db, byteAddr, bit) | BOOL | Read single bit from DB |
S7_WRITE_DB_BYTE(name, db, byteAddr, value) | BOOL | Write unsigned byte |
S7_WRITE_DB_WORD(name, db, byteAddr, value) | BOOL | Write unsigned word |
S7_WRITE_DB_DWORD(name, db, byteAddr, value) | BOOL | Write unsigned double word |
S7_WRITE_DB_INT(name, db, byteAddr, value) | BOOL | Write signed 16-bit integer |
S7_WRITE_DB_DINT(name, db, byteAddr, value) | BOOL | Write signed 32-bit integer |
S7_WRITE_DB_REAL(name, db, byteAddr, value) | BOOL | Write 32-bit float |
S7_WRITE_DB_BOOL(name, db, byteAddr, bit, value) | BOOL | Write single bit to DB |
S7_READ_I(name, byteAddr, count) | []INT | Read input bytes |
S7_READ_Q(name, byteAddr, count) | []INT | Read output bytes |
S7_READ_M(name, byteAddr, count) | []INT | Read marker bytes |
S7_READ_I_BOOL(name, byteAddr, bit) | BOOL | Read input bit |
S7_READ_Q_BOOL(name, byteAddr, bit) | BOOL | Read output bit |
S7_READ_M_BOOL(name, byteAddr, bit) | BOOL | Read marker bit |
S7_WRITE_M(name, byteAddr, values) | BOOL | Write marker bytes |
S7_WRITE_Q(name, byteAddr, values) | BOOL | Write output bytes |
S7_WRITE_M_BOOL(name, byteAddr, bit, value) | BOOL | Write marker bit |
S7_WRITE_Q_BOOL(name, byteAddr, bit, value) | BOOL | Write output bit |
S7_ADD_POLL(name, area, dbNumber, byteAddr, byteCount) | BOOL | Register background poll range |
Server Functions (~14)
| Function | Returns | Description |
|---|---|---|
S7_SERVER_CREATE(name, port) | BOOL | Create named S7 server |
S7_SERVER_START(name) | BOOL | Begin listening |
S7_SERVER_STOP(name) | BOOL | Stop listening |
S7_SERVER_IS_RUNNING(name) | BOOL | Check server state |
S7_SERVER_SET_DB(name, db, byteAddr, values) | BOOL | Write to server DB area |
S7_SERVER_GET_DB(name, db, byteAddr, count) | []INT | Read from server DB area |
S7_SERVER_SET_M(name, byteAddr, values) | BOOL | Write to server marker area |
S7_SERVER_GET_M(name, byteAddr, count) | []INT | Read from server marker area |
S7_SERVER_SET_I(name, byteAddr, values) | BOOL | Write to server input area |
S7_SERVER_GET_I(name, byteAddr, count) | []INT | Read from server input area |
S7_SERVER_SET_Q(name, byteAddr, values) | BOOL | Write to server output area |
S7_SERVER_GET_Q(name, byteAddr, count) | []INT | Read from server output area |
S7_SERVER_DELETE(name) | BOOL | Remove server |
S7_SERVER_LIST() | []STRING | List all servers |
ControlForge v1.0.1064 | Siemens S7 Client + Server | IEC 61131-3 Structured Text